Mains Monitoring, 3-Phase 380 - 415VAC, 2 W 8A – 70.42.8.400.2032
€ 167,88 exkl. USt.
Mains Monitoring, 3-Phase 380 - 415VAC, 2 W 8A – 70.42.8.400.2032 is backordered and will ship as soon as it is back in stock.
3-phase 380-415 V AC monitoring with neutral conductor monitoring (not selectable). Adjustable functions: undervoltage, overvoltage, over/undervoltage range, selectable voltage fault memory, phase sequence, phase failure, phase asymmetry and neutral conductor interruption. Supply voltage operating range 220 - 510 V AC 50/60 Hz. Rated power: 12.5 VA, /1W. Contact: 2 changeover contacts for 8 A. Switch-off delay time adjustable from 0.5-60 seconds. Power-on inhibit time 1 second. Device width 35 mm.
€ 167,88 exkl. USt.
Mains Monitoring, 3-Phase 380 - 415VAC, 2 W 8A – 70.42.8.400.2032 is backordered and will ship as soon as it is back in stock.
Technische Parameter
Technische Parameter
| Asymmetry detection function | Yes | Phase sequence monitoring function | Yes |
| Max. permissible response delay time | 1 s | Type of electrical connection | Screw connection |
| Overvoltage detection function | Yes | Min. adjustable response delay time | 1 s |
| Undervoltage detection function | Yes | Min. adjustable recovery delay time | 0.5 s |
| Width | 35 mm | Voltage measuring range | 300..480 V |
| Number of change-over contacts | 2 | Height | 88.8 mm |
| With removable clamps | No | Max. permissible recovery delay time | 60 s |
| Number of N/C contacts | 0 | Phase failure detection function | Yes |
| Depth | 60.8 mm | Number of N/O contacts | 0 |