ÖLFLEX CLASSIC 110 Orange 4G1 Cut Length
€ 2,25 exkl. USt.
ÖLFLEX CLASSIC 110 Orange 4G1 Cut Length is backordered and will ship as soon as it is back in stock.
According to EN 60204-1 (VDE 0113-1), conductors of control circuits that are supplied by an external voltage source and/or remain live when the main switch is off must be orange. Lighting and socket circuits for maintenance or repair purposes, circuits for undervoltage protection, control circuits for interlocking, Suitable for torsional applications typical in wind turbine (WTG) loops, Space-saving due to small cable diameters, High electrical safety due to 4 kV test voltage, Fine-wired strand of bare copper wires, PVC core insulation LAPP P8/1, Orange cores with black numbers, Sheath: PVC, orange (similar to RAL 2003), Based on IEC 60227-5 and EN 50525-2-51, Flame retardant according to IEC 60332-1-2,
€ 2,25 exkl. USt.
ÖLFLEX CLASSIC 110 Orange 4G1 Cut Length is backordered and will ship as soon as it is back in stock.
Technische Parameter
Technische Parameter
| Cold-resistant according to EN 60811-504+505+506 | Yes | Oil-resistant according to EN IEC 60811-404 | No |
| Supporting element | none | Stranding element | no |
| Fire behaviour according to EN 13501-6: Smoke development | none | Fire behaviour according to EN 13501-6: Class | Eca |
| Halogen-free according to EN IEC 60754-2 | No | Shield over stranding | none |
| Number of cores | 4 | Flame retardant according to IEC 60332-3-25 (Cat D) | No |
| Flame retardant according to IEC 60332-3-23 (Cat B) | No | Flame retardant according to IEC 60332-3-22 (Cat A) | No |
| Torsion protection | No | Sheath material specification | other |
| Permissible external cable temperature during installation/handling | -5..70 °C | Flame retardant according to IEC 60332-3-24 (Cat C) | No |
| With protective conductor | Yes | Core insulation material | Polyvinyl chloride (PVC) |
| Fire behaviour according to EN 13501-6: Acid development | none | Rated voltage U0 | 300 V |
| Min. permissible bending radius, stationary use/fixed installation | 26 mm | Core identification | Digits |
| Shield over stranding element | none | Permissible external cable temperature after installation without vibration | -40..80 °C |
| Fire behaviour according to EN 13501-6: Droplet behaviour | none | Halogen-free according to EN IEC 60754-3 | No |
| Flame retardant according to IEC 60332-1-2 | Yes | Cable geometry | round |
| Sheath material | Polyvinyl chloride (PVC) | Core insulation specification | other |
| Sheath colour | orange | Rated voltage U | 500 V |
| Min. permissible bending radius, flexible use/free movement | 97.5 mm | Outer diameter approx. | 6.5 mm |
| Halogen-free according to EN IEC 60754-1 | No | Low smoke according to EN IEC 61034-2 | No |
| Flame retardant according to IEC 60332-3-21 (Cat A F/R) | No | Conductor class | Class 5 = fine-stranded |
| Conductor material | Copper | Conductor surface | bare |
| Nominal conductor cross-section | 1 mm² |