ABB  Art.Nr: 15433201975627

MS Motor protection circuit breaker trip class 10 1.6-2.5A – 1SAM350000R1007

Regular price
Regular price € 100,54 inkl. USt.
€ 83,78 exkl. USt.
Verfügbarkeit wird geladen …
WhatsApp Sofortberatung Jetzt online Persönliche Beratung direkt vom Fachmann – Antwort meist in wenigen Minuten.
Motor starter protector MS132 with thermal and electromagnetic protection represents the compact and powerful series with high short-circuit breaking capacity for motor protection up to 15 kW (400 V) with a module width of 45 mm. The temperature-compensated device has a rotary handle operation with a clear switch position indicator I/TRIP/0. In addition, the MS132 has a short-circuit indicator. The rotary handle can be locked directly in the 0-position with a padlock. Auxiliary, signal and short-circuit signaling contacts as well as undervoltage and shunt trips can be mounted without tools. 3-phase busbars for 65 A or 100 A and infeed blocks for 25 mm² or 35 mm² allow the common infeed of multiple motor starter protectors. Protective housings and accessories for control cabinet and door mounting complete the range. ATEX certification allows the protection of motors in hazardous areas, UL approval as >self-protected combination motor controller< expands the range of application in North America.>
Installation anfragen
Montage • Elektro • Inbetriebnahme
Wir bieten die Installation deiner Photovoltaikanlage durch unser Team sowie durch ausgewählte Partnerbetriebe an. Gemeinsam sorgen wir für eine fachgerechte Montage, Elektroinstallation und zuverlässige Inbetriebnahme.
Installation anfragen
Datenblatt
Hinweis: Der Link kann je nach Hersteller direkt einen Download starten.
Öffnen / Download

Technische Parameter

Phase failure sensitive Yes Rated operational power at AC-3, 400 V 0.75 kW
With integrated undervoltage release No Rated permanent current Iu 2.5 A
Connection type main current circuit Screw connection Overload release current setting range 1.6..2.5 A
Rated operational voltage 250..690 V Device construction type Complete device in housing
Rated ultimate short-circuit breaking current Icu at 400 V, AC 100 kA With integrated auxiliary switch No
Number of poles 3 Release technology Thermomagnetic
Height 90 mm Type of operating element Rotary knob
Width 45 mm Depth 86.75 mm
Setting range of the instantaneous short-circuit release 31.3..31.3 A With thermal overload protection Yes
Rated operational power at AC-3, 230 V 0.75 kW Power loss 5.4 W
Degree of protection (IP) IP20