ABB
Art.Nr: 15433201975627
MS Motor protection circuit breaker trip class 10 1.6-2.5A – 1SAM350000R1007
Regular price
Regular price
€ 100,54
inkl. USt.
€ 83,78 exkl. USt.
€ 83,78 exkl. USt.
Unit price
Verfügbarkeit wird geladen …
MS Motor protection circuit breaker trip class 10 1.6-2.5A – 1SAM350000R1007 is backordered and will ship as soon as it is back in stock.
Motor starter protector MS132 with thermal and electromagnetic protection represents the compact and powerful series with high short-circuit breaking capacity for motor protection up to 15 kW (400 V) with a module width of 45 mm. The temperature-compensated device has a rotary handle operation with a clear switch position indicator I/TRIP/0. In addition, the MS132 has a short-circuit indicator. The rotary handle can be locked directly in the 0-position with a padlock. Auxiliary, signal and short-circuit signaling contacts as well as undervoltage and shunt trips can be mounted without tools. 3-phase busbars for 65 A or 100 A and infeed blocks for 25 mm² or 35 mm² allow the common infeed of multiple motor starter protectors. Protective housings and accessories for control cabinet and door mounting complete the range. ATEX certification allows the protection of motors in hazardous areas, UL approval as >self-protected combination motor controller< expands the range of application in North America.>
ABB
Art.Nr: 15433201975627
Regular price
Regular price
€ 100,54
inkl. USt.
€ 83,78 exkl. USt.
€ 83,78 exkl. USt.
Unit price
MS Motor protection circuit breaker trip class 10 1.6-2.5A – 1SAM350000R1007 is backordered and will ship as soon as it is back in stock.
Installation anfragen
Montage • Elektro • Inbetriebnahme
Wir bieten die Installation deiner Photovoltaikanlage durch unser Team sowie durch ausgewählte Partnerbetriebe an. Gemeinsam sorgen wir für eine fachgerechte Montage, Elektroinstallation und zuverlässige Inbetriebnahme.
Installation anfragen
Datenblatt
Hinweis: Der Link kann je nach Hersteller direkt einen Download starten.
Technische Parameter
Technische Parameter
| Phase failure sensitive | Yes | Rated operational power at AC-3, 400 V | 0.75 kW |
| With integrated undervoltage release | No | Rated permanent current Iu | 2.5 A |
| Connection type main current circuit | Screw connection | Overload release current setting range | 1.6..2.5 A |
| Rated operational voltage | 250..690 V | Device construction type | Complete device in housing |
| Rated ultimate short-circuit breaking current Icu at 400 V, AC | 100 kA | With integrated auxiliary switch | No |
| Number of poles | 3 | Release technology | Thermomagnetic |
| Height | 90 mm | Type of operating element | Rotary knob |
| Width | 45 mm | Depth | 86.75 mm |
| Setting range of the instantaneous short-circuit release | 31.3..31.3 A | With thermal overload protection | Yes |
| Rated operational power at AC-3, 230 V | 0.75 kW | Power loss | 5.4 W |
| Degree of protection (IP) | IP20 |