Mains monitoring for phase sequence, failure, over-/undervoltage, 380-480VAC – RM22TR33
€ 112,76 exkl. USt.
Mains monitoring for phase sequence, failure, over-/undervoltage, 380-480VAC – RM22TR33 is backordered and will ship as soon as it is back in stock.
HARMONY Control. This grid monitoring relay monitors three-phase networks (380-480 VAC) for phase sequence, phase failure, undervoltage and overvoltage. Two changeover contacts are available for signalling, which can be loaded up to 8 A. A limit value (-20--2%/+2-+20%) can be set for undervoltage and overvoltage respectively, and a response or drop-out delay can be set for the output. Settings are made via controls on the front, which can be protected against changes by a transparent cover. A illuminated scale pointer makes it very easy to see the potentiometer setting even from a distance. The diagnostic switch on the front allows the output relays to be switched off to test the entire application. Closing the transparent cover automatically resets the diagnostic switch. Three LEDs indicate the status. The width is 22.5 mm and mounting is on a DIN rail. The cable connection is made via screw terminals.
€ 112,76 exkl. USt.
Mains monitoring for phase sequence, failure, over-/undervoltage, 380-480VAC – RM22TR33 is backordered and will ship as soon as it is back in stock.
Technische Parameter
Technische Parameter
| With removable clamps | No | Min. adjustable response delay time | 0.1 s |
| Phase sequence monitoring function | Yes | Phase failure detection function | Yes |
| Max. permissible response delay time | 30 s | Number of contacts as normally open contact | 0 |
| Voltage measuring range | 304..576 V | Width | 22.5 mm |
| Asymmetry detection function | No | Number of contacts as normally closed contact | 0 |
| Height | 90 mm | Type of electrical connection | Screw connection |
| Depth | 73 mm | Number of change-over contacts | 2 |
| Under-voltage detection function | Yes | Over-voltage detection function | Yes |
| Max. permissible release delay time | 30 s | Min. adjustable release delay time | 0.1 s |