ÖLFLEX CLASSIC 110 3G1,5 Ring 100 m
€ 121,33 exkl. USt.
ÖLFLEX CLASSIC 110 3G1,5 Ring 100 m is backordered and will ship as soon as it is back in stock.
Fixed installation as well as occasional flexible use without tensile stress with free, non-continuously recurrent movement, Dry or damp rooms, with normal mechanical stress, Suitable for torsion applications typical in the loop of wind turbines (WTG), In power chains for travel distances up to 5 m and 0.2 ... 1 million bending cycles, for the following dimensions: 0.5 to 2.5 mm² and 2 to 7 cores, Wide range of standardized lengths and custom cuts, Very large product range, Designs with up to 100 cores, Fine-wire strand of bare copper wires, PVC core insulation LAPP P8/1, Cores twisted in layers, Sheath: PVC, grey (similar to RAL 7001), VDE Reg. No. 7030 for the following dimensions: up to 2.5 mm²: 2 - 65 cores from 4 mm²: 2 - 7 cores from 25 mm²: 2 - 5 cores, Flame-retardant according to IEC 60332-1-2, Good chemical resistance, Oil-resistant according to DIN EN 50290-2-22 (TM54),
€ 121,33 exkl. USt.
ÖLFLEX CLASSIC 110 3G1,5 Ring 100 m is backordered and will ship as soon as it is back in stock.
Technische Parameter
Technische Parameter
| Nominal conductor cross-section | 1.5 mm² | Conductor class | Class 5 = fine-stranded |
| Number of cores | 3 | Screen over stranding element | without |
| Stranding element | no | Screen over stranding | without |
| Core insulation material | Polyvinyl chloride (PVC) | Core identification | Numbers |
| With protective conductor | Yes | Support element | without |
| Sheath material | Polyvinyl chloride (PVC) | Sheath colour | Grey |
| Cable geometry | Round | Torsion protection | No |
| Low smoke according to EN IEC 61034-2 | No | Fire performance according to EN 13501-6: Class | Eca |
| Oil-resistant according to EN IEC 60811-404 | No | Cold resistant according to EN 60811-504+505+506 | No |
| Outer diameter approx. | 6.7 mm | Min. permissible bending radius, flexible use with guided motion | 100.5 mm |
| Min. permissible bending radius, flexible use/free movement | 67 mm | Min. permissible bending radius, stationary use/fixed installation | 26.8 mm |
| Permissible external cable temperature during installation/handling | -15..70 °C | Permissible external cable temperature after installation without vibration | -40..80 °C |
| Nominal voltage U0 | 300 V | Nominal voltage U | 500 V |
| Weight | 84 kg/km |