DÄTWYLER  Art.Nr: 15432997077323

Fire alarm cable with circuit integrity max. 225V FE180 E30 red Cut length

Regular price
Regular price € 4,07 inkl. USt.
€ 3,39 exkl. USt.
Unit price€ 4.070,00 /1000m
Verfügbarkeit wird geladen …
WhatsApp Sofortberatung Jetzt online Persönliche Beratung direkt vom Fachmann – Antwort meist in wenigen Minuten.

Fire alarm cables - Installation cables for industrial electronics, max. 225V. Ceramic safety cables are used wherever special protection against fire and fire damage for people and property is necessary and high safety requirements must be met. They may be installed indoors. When installing outdoors, protection against direct sunlight must be provided. The installation cables comply with the requirements for functional integrity E30* according to DIN 4102-12. Functional integrity is guaranteed at an operating voltage of up to 110 V, e.g., for signal and control systems, public address and smoke and heat extraction systems. Permissible operating temperature at the conductor +70°C.

Installation anfragen
Montage • Elektro • Inbetriebnahme
Wir bieten die Installation deiner Photovoltaikanlage durch unser Team sowie durch ausgewählte Partnerbetriebe an. Gemeinsam sorgen wir für eine fachgerechte Montage, Elektroinstallation und zuverlässige Inbetriebnahme.
Installation anfragen
Datenblatt
Hinweis: Der Link kann je nach Hersteller direkt einen Download starten.
Öffnen / Download

Technische Parameter

Conductor diameter 0.8 mm Conductor class Class 1 = solid
Number of cores 8 Number of stranding elements 4
Stranding element Pairs Core insulation material Polyolefins
Core identification Colour Shield over stranding element None
Shield over lay-up Foil Cable longitudinal water-tight No
Cable transverse water-tight No Protective sheath None
Sheath material Polyolefins Sheath colour Red
Outer diameter approx. 8.7 mm Min. permissible bending radius, stationary use/fixed installation 70 mm
Permissible cable outer temperature during installation/handling -5..50 °C Permissible cable outer temperature after installation without vibration -5..70 °C
Suitable as telephone cable Yes Weight 103 kg/km