DÄTWYLER  Art.Nr: 15433118941515

Cable with functional integrity FE180 E30 with concentric conductor cut length

Regular price
Regular price € 8,21 inkl. USt.
€ 6,84 exkl. USt.
Unit price€ 8.210,00 /1000m
Verfügbarkeit wird geladen …
WhatsApp Sofortberatung Jetzt online Persönliche Beratung direkt vom Fachmann – Antwort meist in wenigen Minuten.

Safety cable with concentric conductor, 0.6/1kV, Ceram, halogen-free, with improved fire behavior, in accordance with VDE 0266, insulation integrity FE180 according to VDE 0472-814, IEC 60331, functional integrity E30-E60* according to DIN 4102-12. Safety cables are used wherever special protection against fire and fire damage to people and property is necessary and high safety requirements must be met. They may be laid indoors. When laid outdoors, protection against direct sunlight must be provided (orange jacket color). Direct laying in soil and water is only permitted with the use of a protective conduit. These cables comply with the requirements for functional integrity E30-E60* according to DIN 4102-12. Functional integrity is guaranteed at an operating voltage of up to 400 V. Permissible operating temperature at the conductor +90°C.

Installation anfragen
Montage • Elektro • Inbetriebnahme
Wir bieten die Installation deiner Photovoltaikanlage durch unser Team sowie durch ausgewählte Partnerbetriebe an. Gemeinsam sorgen wir für eine fachgerechte Montage, Elektroinstallation und zuverlässige Inbetriebnahme.
Installation anfragen
Datenblatt
Hinweis: Der Link kann je nach Hersteller direkt einen Download starten.
Öffnen / Download

Technische Parameter

Conductor material Copper Nominal conductor cross-section 2 mm²
Conductor class Class 1 = solid Conductor shape round
Number of cores 3 Core identification Colour
With protective conductor No Screen No
Drain wire No Lead sheath No
Number of auxiliary conductors 0 Concentric conductor Copper
Nominal cross-section of concentric conductor 2.5 mm² Sheath material Polyolefin
Sheath colour orange Outer diameter approx. 14 mm
Min. permissible bending radius, stationary use/fixed installation 168 mm Weight 380 kg/km
Max. permissible conductor temperature 90 °C Permissible external cable temperature during assembly/handling -5..90 °C
Nominal voltage U0 0 kV Nominal voltage U 1 kV